Screen copper or aluminium rectangular busbar sizes from current or transformer kVA, with short-time conductor fault heating and clear IEC 61439 verification limits.
EstimatePreliminary result, not a design verification.
Before you calculate
LV busbar sizing: thermal area vs fault stress
Screen standard copper and aluminium rectangular bar arrangements for a known current or transformer kVA. A/mm² screening is not an IEC 61439 current rating; always verify enclosure temperature rise, joints and peak mechanical short-circuit withstand.
Rectangular bare Cu/Al busbars in a low-voltage distribution assembly. The calculated size is a preliminary area screening — not a manufacturer-verified continuous current rating.
Used to convert kVA to A; no power factor is needed.
Focused on the two common LV panel bar thicknesses. Width and number of bars are selected separately.
Editable planning assumption, NOT an IEC 61439 ampacity value.
Step 2 · Short-circuit heat
Prospective fault current
Screening assumptions: 25 kA / 1 s and 70 → 160°C are illustrative defaults, not site data or universal permissible busbar temperatures. Confirm the actual short-circuit duty, connections, insulation and support limits.
Step 3 · Preliminary result
Busbar selection
Design line current1,600 A
Minimum combined area requirement1,333.3 mm²
Minimum area-screened option3 × 100 × 5 mm
Per phase · 1,500 mm² total area · 1.067 A/mm² at design current
15% screening headroom option2 × 80 × 10 mm
Per phase · 1,600 mm² total area · 1 A/mm² at design current
Current-density area requirement1,333.3 mm²
Adiabatic fault area requirement217.4 mm²
Conductor k (selected temperatures)115 A√s/mm²
Engineering checks still required before approval
Continuous thermal rating: verify in the real enclosure under IEC 61439, including bar spacing, ambient, ventilation and joints. Mechanical short-circuit withstand: verify peak current (Ipk), phase spacing, support strength and span under IEC 60865 / verified assembly design. Additional: AC skin/proximity losses, earthing and N/PE bars, connection temperature, clearance and creepage.
1 · Convert kVA to current, if applicable
Three-phase apparent power does not require cos φ.
I=3ULLS
Idesign=1,600A
2 · Current-density area screening (not ampacity)
AJ=JscreenI
AJ=1.21,600=1,333.33mm2
3 · Bare-metal adiabatic fault heating
k=Cln(B+θiB+θf)
Ak=kIkt=115.00425×1000×1=217.38mm2
4 · Select standard geometry from both criteria
Amin=max(AJ,Ak)=1,333.33mm2
Aheadroom=max(Ak,AJ(1+15/100))=1,533.33mm2
Select a rectangular bar width, the chosen 5/10 mm thickness and number per phase meeting the required combined metal area. Equal current sharing is assumed for parallel bars, but must be demonstrated for a real assembly.