MV Cable Sizing
Preliminary Cu/Al XLPE sizing for directly buried and ducted 10–30 kV cables, with engineering assumptions and worked formulas.
Understanding MV cable sizing
Select one XLPE single-core cable per phase for 10, 20 or 30 kV. Compare preliminary reference ampacity and indicative voltage drop under fixed, clearly stated buried reference conditions. Conductor short-circuit heating and metallic-screen checks need separate verification.
MV cable selection
Choose the cable arrangement, enter the transformer nameplate kVA or feeder current, then verify the site-specific cable rating with the manufacturer.
Advanced electrical checks
The phase-conductor check uses IEC-type adiabatic k factors (Cu XLPE: 143; Al XLPE: 94 A·√s/mm² at 90→250°C). Earth faults heat the copper screen differently: its size, fault share, bonding and clearing time are separate checks.
Thermal cable screening
For example, a 1,000 kVA transformer at 20 kV draws just 28.87 A at nominal full load. A 35 mm² conductor can exceed that current thermally, but that alone does not establish its suitability. For this 20 kV copper example, an illustrative 10 kA / 1 s duty raises the phase-conductor screening minimum to 70 mm² Cu. The final cross-section depends on the actual short-circuit current and clearing time; also check the copper screen, actual 12/20 kV cable rating, installation conditions and utility requirements. The conductor fault check is based on your entered or illustrative assumed duty; screen protection remains unverified.
Tabulated values are reference-condition screening, not a manufacturer-certified rating or a complete IEC 60287 study. The voltage-drop model shows a power-factor-independent conservative bound using hot DC resistance rather than full AC impedance. The metallic screen is NOT sized here: its copper screen area, earth-fault current contribution, bonding configuration and fault clearing time need a separate thermal and protection check. Site-specific soil and duct construction also remain unverified.
1. Determine the design current
Convert the known three-phase apparent power (kVA) to line current at the selected line-to-line voltage.
2. Compare load current with reference ampacity
The chosen reference table assumes the exact buried geometry, ground temperature and resistivity stated above. No unverified ambient or soil correction has been applied.
Practical headroom setting: 15% above design current (optional design preference).
3. Estimate hot-conductor resistance
The cable's DC resistance is adjusted to the reference maximum XLPE conductor temperature. AC skin, proximity and screen effects are not yet included.
4. Estimate voltage drop
Without an entered power factor, we use a conservative first-order bound based on the magnitude of R + jX. It is not the predicted voltage drop at the actual operating power factor. Manufacturer AC impedance is required for detailed design.
5. Check conductor thermal short-circuit withstand
An indicative adiabatic check only, applicable within its assumptions. The metallic screen has a different cross-sectional area and separate fault duty.
- Note for 12/20 and 18/30 kV: the reference ratings are calculated for 6/10 kV cables. A Prysmian catalogue lists the same aluminium ratings for 6/10, 12/20 and 18/30 kV but states they were calculated for 6/10 kV, so confirm the rating of the actual product on its manufacturer datasheet.
Scope and assumptions of this screening (6)
- Preliminary screening only: the reference ampacities are for one balanced 50 Hz circuit at 20°C soil temperature, 1.5 K·m/W soil resistivity, 0.8 m burial depth, both-end-bonded screens and the specified arrangement.
- Direct-buried flat reference assumes one cable outside diameter of spacing between the three phase cables.
- Voltage-drop value is a conservative, power-factor-independent first-order bound using hot DC resistance, not the predicted voltage drop at a known power factor. AC impedance and actual operating power factor must be checked for the completed design.
- The prospective three-phase fault current and total heating duration must come from the site/network study and actual protection behavior. A software preset is NOT an average for the Greek grid or a verified fault level.
- Metallic-screen earth-fault thermal withstand, bonding losses, short-circuit protection/disconnection and installation-specific derating require independent verification.
- The IEC 60502-2:2014 reference table values represent model cables, not a certified ampacity for any specific VOP product. Verify against manufacturer data and the current standard edition.
References & assumptions
The reference-condition ampacity subset is attributed to public technical presentations of IEC 60502-2:2014 Annex B (model cable ratings calculated for 6/10 kV), with physical cable examples from VOP. The trefoil and three-core arrangements come from the Prysmian medium-voltage catalogue (a distributor-hosted copy; its edition is not stated); its single-core flat values agree with Annex B. For 20 kV, verify the actual 12/20 kV cable. Commercial deployment requires independent standards/data licensing review and technical validation.