PE Conductor Sizing
IEC 60364-5-54 table, adiabatic check with k chosen for the conductor size and installation, and separate Cu/Al PE minimums.
Protective earth conductor sizing
Compare the simplified same-material sizing table with an adiabatic fault thermal check. The appropriate method depends on installation conditions and protection design.
PE conductor sizing
Compare the IEC 60364-5-54 simplified same-material table against an adiabatic short-circuit check (k chosen automatically from the tables, or your own). Confirm the fault current that actually flows through PE and the protective-device clearing energy.
Required conductor area
Adiabatic equation
k = 143 for the selected 35 mm² conductor (XLPE/EPR, copper, bunched or in a cable; tables: 143 up to 300 mm², 143 above).
Same-material table screening
This table requires its prescribed installation and material conditions; not automatically asserted when material or installation conditions differ; adiabatic calculation and separate-conductor minima remain applicable.
Scope and assumptions (1)
- Confirm the actual installation-specific k, fault I²t/clearing time, earthing arrangement and protective path. This is a sizing screen, not an installation approval.