Reactive Components (C / L) — Capacitors & Reactors
Convert capacitor-bank or reactor kvar to C/L, calculate delta/star branch values, and estimate kvar from isolated L-L measurements.
Capacitance, inductance and kvar
Choose Capacitive (C) or Inductive (L). Convert between nameplate kvar and equivalent terminal measurements, or enter isolated L-L readings to estimate reactive power. Ideal balanced-network assumptions apply.
Capacitive or inductive?
Capacitor-bank capacitance and capacitive kvar — including L-L field measurements.
Important: measure only after isolation, discharge (capacitors), lockout, and verification of a safe de-energized state. Disconnect external components. Detuned banks, internal series/parallel units, discharge networks and coupled inductors need their own test method.
Calculated results
Nominal calculation at the entered voltage and frequency, without resistive losses or external reactors.
Step-by-step mathematics
1. Convert the rating to a terminal measurement
Calculate the expected line-to-line reading with the third phase left floating.
2. Derive the actual delta branch value
The meter sees one capacitor in parallel with the other two in series.
3. Calculate reactance and line current
This is the ideal reactive component only; real resistance, loss and harmonic behaviour require a separate analysis.
Calculations use full numerical precision; only displayed values are rounded.