Transformer Tap Adjustment
Predicted LV voltage at each MV tap, from a measurement.
EstimatePreliminary result, not a design verification.
Before you calculate
Learn more — complete guide →Predicted LV voltage at each MV tap
From a measured LV voltage and the nameplate tap voltages. A planning estimate; off-circuit taps are changed only de-energized under the approved procedure.
Step 1
Transformer and measurement
Enter the MV tap voltages printed on the nameplate and the LV voltage you measured. The default tap list is an ILLUSTRATIVE 20 kV ± 2 × 2.5 % pattern.
The voltage the tool aims for: the tap closest to it is shown.
Advanced: your nameplate tap list and three-phase readings (optional)
Comma-separated; position labels optional as position:kV. Position numbers have no universal direction.
Your own tolerance; it decides whether the nearest tap counts as reaching the target.
Step 2
Results
Check before relying on this result
- Off-circuit (off-load) tap changers must never be operated energized. Follow the transformer manual and the switching procedure: isolation, proving dead, earthing, qualified personnel.
Nearest MV tap to the target19.5 kV-2.5 % of rated · target inside the tap span
Expected LV voltage (ratio estimate)400.0 VSigned difference from the target 0.0 V · within your ±2 V
| MV tap | % of rated | Predicted LV | Difference | Note |
|---|---|---|---|---|
| 21 kV | 5.0 % | 371.4 V | -28.6 V | |
| 20.5 kV | 2.5 % | 380.5 V | -19.5 V | |
| 20 kV | 0.0 % | 390.0 V | -10.0 V | current |
| 19.5 kV | -2.5 % | 400.0 V | 0.0 V | nearest to target |
| 19 kV | -5.0 % | 410.5 V | 10.5 V |
Planning estimate, not a switching instruction. The real voltage after the change also depends on the grid provider's supply voltage, the load and its power factor, and the transformer's regulation. Off-circuit taps are changed only de-energized, under the approved procedure, by qualified personnel.
1. Predicted LV voltage at another tap
Ideal ratio model: same incoming MV voltage and similar load before and after. A lower MV tap voltage gives a higher LV voltage.
2. Difference from the target
The tap with the smallest absolute difference in the list is shown as the nearest.
Calculations use full precision internally; the displayed numbers are rounded for readability.