MV Transformer Protection Settings (50/51/50N/51N)
Reference pickups in ABB REF615 format; reference only, not for commissioning.
Reference pickups for MV transformer protection
REFERENCE VALUES ONLY — NOT FOR COMMISSIONING. Illustrative 50/51/50N/51N pickups from editable demonstration multipliers, converted to the ABB REF615 Start value format. Real settings come from a protection-coordination study and the grid provider requirements.
Transformer and CTs
Advanced: demonstration multipliers, curves, delays, Start value Mult, test currents
The multipliers are ILLUSTRATIVE demonstration values, not IEC settings and not recommendations.
Reference results
- REFERENCE VALUES ONLY — NOT FOR COMMISSIONING. Final settings need a protection-coordination study with the real fault levels, CT and relay data, inrush, the upstream and downstream devices and the grid provider requirements.
- The 50 pickup is 10.0 × the CT rated secondary current: CT burden, accuracy limit, saturation and the relay input limits must be verified before such a value means anything.
| Function block | Start value | Start value Mult | ENA_MULT (simulated) | Operating curve type | Time multiplier | Operate delay time | Minimum operate time | Io signal Sel |
|---|---|---|---|---|---|---|---|---|
| PHLPTOC (51) | 0.58 × In | 1 | Inactive | 9 = IEC Normal (Standard) Inverse | 0.1 | — | 20 ms | — |
| PHIPTOC (50) | 10.01 × In | 1 | Inactive | 15 = IEC Definite Time | — | 50 ms | — | — |
| EFLPTOC (51N) | 0.200 × In | 1 | Inactive | 9 = IEC Normal (Standard) Inverse | 0.1 | — | 20 ms | 2 = Calculated Io |
| EFIPTOC (50N) | 1.00 × In | 1 | Inactive | 15 = IEC Definite Time | — | 50 ms | — | 2 = Calculated Io |
1. Rated MV current
From the nameplate power and the MV line-to-line voltage.
2. Estimated MV current during an LV short circuit
Transformer impedance only, ideal stiff MV supply: not the network short-circuit level.
3. ABB Start value from a primary pickup
Divide by the CT primary, round to the function step; never clamped.
4. 51 inverse time at the test current
IEC 60255-151 curve; excludes relay tolerance, outputs and the breaker.
Calculations use full precision internally; the displayed numbers are rounded for readability.