Interactive calculator

MV Transformer Protection Settings (50/51/50N/51N)

Reference pickups in ABB REF615 format; reference only, not for commissioning.

EstimatePreliminary result, not a design verification.
Before you calculate

Reference pickups for MV transformer protection

REFERENCE VALUES ONLY — NOT FOR COMMISSIONING. Illustrative 50/51/50N/51N pickups from editable demonstration multipliers, converted to the ABB REF615 Start value format. Real settings come from a protection-coordination study and the grid provider requirements.

Learn more — complete guide →
Step 1

Transformer and CTs

From the nameplate; 6 % is not a universal value.
Advanced: demonstration multipliers, curves, delays, Start value Mult, test currents

The multipliers are ILLUSTRATIVE demonstration values, not IEC settings and not recommendations.

Above it the inverse time no longer decreases.
Step 2

Reference results

Check before relying on this result
  • REFERENCE VALUES ONLY — NOT FOR COMMISSIONING. Final settings need a protection-coordination study with the real fault levels, CT and relay data, inrush, the upstream and downstream devices and the grid provider requirements.
  • The 50 pickup is 10.0 × the CT rated secondary current: CT burden, accuracy limit, saturation and the relay input limits must be verified before such a value means anything.
Rated MV current46.19 ACT secondary at rated load: 2.309 A
Estimated MV current during an LV short circuit769.8 ATheoretical MV-side symmetrical current for a three-phase fault at the transformer LV terminals, considering transformer impedance only and an ideal stiff MV supply.
51 (PHLPTOC) reference pickup0.58 × InTheoretical 57.74 A (0.57735 × In) → 58 A primary / 2.9 A secondary · CT 100/5 AIEC Normal (Standard) Inverse, code 9 · raw IEC t ≈ 0.318 s · ABB-adjusted reference ≈ 0.318 s · ABB-adjusted reference time; the raw IEC equation gives 0.3180 s. Excludes relay tolerance, outputs and the breaker. ENA_MULT inactive: base pickup.REFERENCE VALUES ONLY — NOT FOR COMMISSIONING.
50 (PHIPTOC) reference pickup10.01 × InTheoretical 1000.74 A (10.0074 × In) → 1001 A primary / 50.05 A secondary · CT 100/5 ADefinite time · No pickup from this element at the test current. ENA_MULT inactive: base pickup.REFERENCE VALUES ONLY — NOT FOR COMMISSIONING.
51N (EFLPTOC) reference pickup0.200 × InTheoretical 20.00 A (0.2 × In) → 20 A primary / 1 A secondary · CT 100/5 AIEC Normal (Standard) Inverse, code 9 · raw IEC t ≈ 0.428 s · ABB-adjusted reference ≈ 0.428 s · ABB-adjusted reference time; the raw IEC equation gives 0.4280 s. Excludes relay tolerance, outputs and the breaker. ENA_MULT inactive: base pickup.REFERENCE VALUES ONLY — NOT FOR COMMISSIONING.
50N (EFIPTOC) reference pickup1.00 × InTheoretical 100.00 A (1 × In) → 100 A primary / 5 A secondary · CT 100/5 ADefinite time · No pickup from this element at the test current. ENA_MULT inactive: base pickup.REFERENCE VALUES ONLY — NOT FOR COMMISSIONING.
ABB parameters per function block (REF615 5.0 FP1 IEC) — reference only; check the real firmware and PCM600 configuration
Function blockStart valueStart value MultENA_MULT (simulated)Operating curve typeTime multiplierOperate delay timeMinimum operate timeIo signal Sel
PHLPTOC (51)0.58 × In1Inactive9 = IEC Normal (Standard) Inverse0.1—20 ms—
PHIPTOC (50)10.01 × In1Inactive15 = IEC Definite Time—50 ms——
EFLPTOC (51N)0.200 × In1Inactive9 = IEC Normal (Standard) Inverse0.1—20 ms2 = Calculated Io
EFIPTOC (50N)1.00 × In1Inactive15 = IEC Definite Time—50 ms—2 = Calculated Io
About these parameters: each block has its own Start value Mult, and it acts only while that block's ENA_MULT input is active (simulated here). General setting IDMT Sat point = 50. Not every REF615 configuration has every block or a sensitive Io input. Source: ABB 615 series Technical Manual 1MRS756887 rev Q (2023-03-06), product version 5.0 FP1; Stage ranges and steps, curve codes and IEC coefficients were compared with the PDF (1MRS756887 rev Q) by the owner's independent reviewer (v0.1.72 validation report); the TMS, Start value Mult and CT-primary steps, Minimum operate time 20 to 60000 ms and IDMT Sat point 10 to 50 come from the same review (pp. 48-49, 55, 220, 231-233, 311, 316-319, 1132-1136). KiloVolt has not itself read the PDF.
Not established here: the real maximum and minimum MV fault currents, the inrush waveform, 50 sensitivity and selectivity, earth-fault settings in isolated, resonant or impedance-earthed networks, CT accuracy and saturation, coordination with the grid provider fuses or relays. Earth-fault currents cannot be inferred from kVA and uk.

1. Rated MV current

From the nameplate power and the MV line-to-line voltage.

In,MV=Sn3 UMVI_{n,MV}=\frac{S_n}{\sqrt{3}\,U_{MV}}
In,MV=16003×20=46.188 AI_{n,MV}=\frac{1600}{\sqrt{3}\times 20}=46.188\ \text{A}

2. Estimated MV current during an LV short circuit

Transformer impedance only, ideal stiff MV supply: not the network short-circuit level.

Ik,MV≈In,MVuk/100I_{k,MV}\approx\frac{I_{n,MV}}{u_k/100}
Ik,MV≈46.1880.06=769.8 AI_{k,MV}\approx\frac{46.188}{0.06}=769.8\ \text{A}

3. ABB Start value from a primary pickup

Divide by the CT primary, round to the function step; never clamped.

Start value=round ⁣(IpickupICT,pri, step)×In\text{Start value}=\mathrm{round}\!\left(\frac{I_{pickup}}{I_{CT,pri}},\ \text{step}\right)\times I_n
57.735100=0.57735 → 0.58×In\frac{57.735}{100}=0.57735\ \rightarrow\ 0.58\times I_n

4. 51 inverse time at the test current

IEC 60255-151 curve; excludes relay tolerance, outputs and the breaker.

t=TMS kMα−1,M=IIpickupt=TMS\,\frac{k}{M^{\alpha}-1},\quad M=\frac{I}{I_{pickup}}
t=0.1×0.14(500/58)0.02−1=0.318 st=0.1\times\frac{0.14}{(500/58)^{0.02}-1}=0.318\ \text{s}

Calculations use full precision internally; the displayed numbers are rounded for readability.