Cable sizing is not simply picking a conductor that can carry the load current. The cable must also remain within its temperature limit, deliver adequate voltage, survive faults and work correctly with its protective device.
We'll build the idea one step at a time. The KiloVolt calculator is a screening assistant: the quick mode recommends a preliminary minimum from a limited set of IEC-based reference ratings, while the advanced mode lets you verify a specific cable using manufacturer data.
Minimum cable, recommended cable and parallel alternatives
Start with the Quick Cable Selection. Enter your load current (up to 1,500 A), cable length, supply voltage, insulation, material and actual installation arrangement. Parallel runs are selected automatically unless you specify a fixed number to inspect.
The engine checks each available conductor's IEC-based reference ampacity, ambient-temperature correction, grouping factors and voltage drop for the specified method. A preliminary candidate must pass both checks:
Minimum IEC-based cable identifies a passing preliminary arrangement with no additional voluntary thermal headroom. To avoid the impractical mathematical solution of dozens of very small cables, this searches the fewest feasible run count and at most one additional parallel set. It is a screening minimum within these practical limits, not a guaranteed globally minimal or IEC-certified design.
Recommended cable requires your selected thermal headroom (15% by default) and prefers fewer parallel runs. Recommended Option 2 only appears when a valid arrangement using a limited number of extra parallel runs genuinely reduces conductor cross-section per phase. Limiting the number of additional runs and the selectable thermal headroom are KiloVolt design choices, not IEC requirements.
When one cable cannot meet the specified load and voltage drop, the search automatically considers parallel conductors without pretending the installation method has changed. Up to 20 bunched/enclosed B2 runs or up to nine single-layer C/E runs are screened, following the limited correction-factor data. Method F can compare up to three perforated trays automatically, clearly reporting the number of separate trays assumed; you may instead restrict the calculation to a fixed tray count. This is a proposed layout, not confirmation that the required trays exist at the site. This is an extension of feeder-current selection to 1,500 A, not a fictitious 1,500 A ampacity for one cable.
These comparisons are not cost estimates. The comparison counts PHASE-conductor metal area only. It ignores neutral/PE conductors, insulation, installation labour, glands, lugs, switchgear terminations, cable support and loss costs. More than nine grouped C/E runs are not automatically assigned a grouping factor in this version; they require a separate layout analysis. At very high currents also compare busbar trunking and verify thermal interaction, electromagnetic forces and equal current sharing.
What does cable sizing actually mean?
Think of a cable as a pipe carrying electrical current. Passing current through the conductor produces heat. How much heat the cable can safely release depends on the conductor size, insulation, installation method, ambient conditions and nearby cables.
A large conductor in open air may carry more current than that same cable packed tightly among many other loaded cables. That's why selecting only by cross-sectional area (mm²) is not enough.
Ib
Design currentHow much current does the load draw?
Iz
Corrected ampacityHow much current can this installed cable carry?
In
Protective ratingWhat is the rating or long-time setting of its protection?
Four checks for one cable
Four separate calculations answer different questions. For a fully verified design, none should be skipped merely because another has passed. The quick KiloVolt recommendation deliberately limits its outputs to phase conductor sections, not neutral/PE design.
There are further installation-specific checks too, including disconnection times, neutral/PE conductors, thermal environment, fire performance and manufacturer installation instructions.
Why cable installation method matters
The reference current rating, usually denoted Iz,ref, is the rated current for a particular cable and reference installation condition. For example, a multicore cable in a conduit will not necessarily have the same rating as single-core cables installed on cable ladder.
Enclosures can restrict heat escape; use the appropriate installation reference method.
More heat can escape than from a tightly enclosed cable, but the actual surface and spacing matter.
Open-air installation helps cooling, but closely spaced parallel circuits may need substantial grouping corrections.
Soil thermal resistivity, depth, spacing and soil temperature must be accounted for.
Why do we multiply the cable rating by correction factors?
Reference ampacity is usually stated for specific reference conditions. A higher ambient temperature or a group of nearby loaded cables can reduce the permissible current. Appropriate correction factors account for those differences.
Here n is the number of parallel cable paths, kT represents ambient/soil temperature, kG represents grouping and kO any additional applicable factor. Each factor must match the same reference ampacity basis.
If a manufacturer already publishes a rating for the actual grouped installation, don't apply the same grouping reduction again. Double-derating is also a mistake.
Using multiple parallel cables per phase
Imagine an LV board with a 900 A design current. Instead of one enormous conductor, an engineer may consider 3 × 240 mm² copper per phase. In an ideal, perfectly balanced arrangement, each of the three parallel cables carries one third of the total current.
But three runs do not automatically give triple ampacity. The cables exchange heat, and AC single-core cable geometry influences impedance. They need compatible materials, cross-sections, lengths, routing and terminations. Symmetric cable placement helps equalize AC impedance; the protection scheme must also be compatible.
What Pass, Review and Not assessed mean
The verification checks use the same badges as every KiloVolt calculator. Pass means the check was calculated and met. Review means a limit was exceeded and the design must be changed or justified. Not assessed means a required input, such as the reference ampacity or the protective-device rating, was not entered, so the check could not be made; it is never a pass. Messages that always apply to the method are kept in the collapsed “Scope and assumptions” panel. See how to read the results.
Why cable size also affects voltage drop
A cable with sufficient current capacity can still have excessive voltage drop if it's long. Higher resistance and reactance produce larger voltage changes at the receiving end.
Here L is the one-way length in kilometres, R and X are per-run impedance terms in Ω/km, and the displayed expression assumes an inductive load. The basic two-wire AC circuit uses a factor of 2 instead of √3; a two-wire DC circuit uses the resistive term only.
Remember to add upstream feeder contributions and apply project-specific voltage-drop criteria. KiloVolt labels the percent limit as your selected target, not a universal limit.
Open the separate Voltage Drop Calculator →How the cable and its protective device must work together
When overload protection is required, the device must carry normal load without nuisance trips and also protect the installed cable from overheating. The standard conditions are commonly expressed as:
I₂ is the current that ensures operation within the device's specified conventional time. It depends on the protective device and standard; it is not always 1.45 × In. For adjustable breakers, the relevant long-time current setting is often the meaningful In input.
A cable may pass its voltage-drop check but fail breaker coordination. Treat the results as independent checks.
Why faults require another cable check
During a short circuit, thousands of amperes may flow for a short time. The copper or aluminium conductor heats rapidly. Under the correct assumptions, the adiabatic equation provides a preliminary withstand check:
S is cross-sectional area in mm², Ik is fault current in amperes, t is clearing time in seconds, and k depends on conductor material and permissible temperature rise. With equal fault-current division across n identical paths, the per-run required area becomes:
For PVC conductors larger than 300 mm² the permitted short-circuit final temperature is lower (140 °C instead of 160 °C), so the calculator uses k ≈ 103 for copper and k ≈ 68 for aluminium; XLPE values do not change. These are commonly used approximate insulated phase-conductor k factors for conventional temperature assumptions. They aren't universal for all constructions or starting temperatures. The equation is not a substitute for actual device let-through I²t curves, fault-current division analysis or protection verification.
The neutral conductor: how big should it be?
Everything so far sized the phase conductors. In a three-phase four-wire circuit there is also a neutral, and it is chosen after the phase size is known. It is not simply “the same as the phase” and not automatically “half the phase”: it depends on what the loads do.
Why the neutral is different
With three equal, purely linear loads the three phase currents cancel in the neutral and it carries almost nothing. Real circuits are not like that. Single-phase loads are never shared perfectly between the phases, and electronic loads such as computers and LED drivers draw current in short pulses that are rich in triplen harmonics (the 3rd, 9th, 15th…). These are single-phase, line-to-neutral loads. A conventional three-phase, three-wire variable-speed drive has no neutral connection: it injects characteristic line harmonics (5th, 7th, 11th…) into the phase conductors, which matter for heating and for the supply, but it does not load a neutral with triplen current.
Triplen harmonics: why many neutrals stay full size
The fundamental currents of the three phases are 120° apart, so they cancel in the neutral. A third-harmonic current is different: in all three phases it reaches its peak at the same instant, so the three contributions are in step and add. For identical phases the neutral carries about three times the triplen current of one phase:
Example A: why a reduced neutral cannot be assumed acceptable
Each phase carries 100 A of fundamental current plus 20 A of third harmonic (20 % third-harmonic content). The fundamental cancels in the neutral, but the third harmonic does not:
In this illustrative balanced case the neutral carries 60 A of third-harmonic current even though the fundamental currents cancel. Whether a reduced neutral is acceptable depends on the neutral's temperature-corrected current rating and the harmonic assessment under IEC 60364-5-52 clause 524.3 / Annex E. This example alone cannot establish a compliant neutral size.
When the neutral must be the same size as the phase
- Single-phase circuits, where the neutral carries the whole load current.
- Three-phase circuits whose phase conductors are up to 16 mm² copper or 25 mm² aluminium.
- Circuits for which the neutral current, thermal conditions or harmonic assessment does not justify reduction; a full-size or larger neutral may be necessary.
When a smaller neutral may be considered
Only for larger phase conductors, and only if all of these are true (IEC 60364-5-52 clause 524, as understood here; check the clause and the national annex):
- the phase conductors are larger than 16 mm² Cu or 25 mm² Al;
- the load is practically balanced between the phases;
- the neutral current, including harmonics, stays within the current rating of the smaller neutral in your installation;
- applicable neutral overcurrent protection and disconnection rules are met;
- the neutral is at least 16 mm² Cu / 25 mm² Al AND at least half the phase section.
Summaries of IEC 60364-5-52:2009/AMD1:2024 (CENELEC HD 60364-5-52:2011/A1:2025) give two mandatory minimum-area conditions when a reduced neutral is permitted: at least 16 mm² Cu / 25 mm² Al, and not less than 50% of the phase area. These are necessary, not sufficient, conditions. For triplen harmonics, the standard refers to its normative Annex E with harmonic-dependent reduction factors and thermal requirements. Do not treat 15% and 33% as universal design cutoffs. Earlier editions (IEC 60364-5-52:2009 and HD 60364-5-52:2011) required only the 16 mm² Cu / 25 mm² Al floor, so a project designed under those editions may not require the half-phase minimum; the licensed text and the national adoption (ELOT) decide.
Example B: a 95 mm² copper phase
Phase conductors 95 mm² Cu, balanced load, 5 % third harmonic, neutral protected.
The 2024 IEC minimum from the combined area rules is the next standard size, 50 mm². In practice you would select an available construction, such as 3 × 95 + 50 mm², only after verifying the neutral current, harmonic derating, thermal conditions and protective requirements. Example A illustrates why harmonic assessment is necessary; it does not determine a unique section.
What the calculator shows
Under a three-phase recommendation, LV Cable Sizing shows a collapsed “Neutral conductor” block that applies these rules to the phase size you selected. It asks for nothing and reports no pass or fail: it only tells you whether the neutral must equal the phase and, if not, the combined 2024 IEC minimum section (material floor and half-phase limit). It does not cover TN-C systems (PEN conductor) or several cables per phase, where the neutral arrangement is a design decision.
Example: 900 A feeder with 3 × 240 mm² copper per phase
Consider a balanced 400 V feeder, 25 m long, with an XLPE-insulated copper conductor arrangement. The values 500 A reference ampacity, 0.91 ambient factor and 0.75 grouping factor are hypothetical illustrative inputs, not manufacturer ratings for a real cable. With three cables per phase the neutral arrangement is a design decision, so this example sizes the phase conductors only (see chapter 09 for the neutral).
Current per run
Corrected total current capacity
Because 900 ≤ 950 ≤ 1,023.75 A, the illustrated long-time setting satisfies the first overload condition.
Estimated voltage drop
The voltage-drop estimate is small for this illustrative 25 m run. Actual cable AC impedance must still be checked.
Thermal minimum area per run
Passing this short-duration thermal estimate alone does not establish that the installation is safe.
Common mistakes to avoid
No. Grouping and ambient conditions affect the corrected current capacity.
No. The reference ampacity input is per run; KiloVolt multiplies by the number of parallel paths.
Also check drop, protection, fault withstand and any relevant installation-specific requirements.
In must also coordinate with corrected Iz, and I₂ must be checked where required.
Only for linear, balanced loads. Triplen harmonics from electronic loads add in the neutral and can make it carry as much as, or more than, a phase conductor.
Size alone does not allow a reduction. The load must be balanced, harmonics low and the neutral protected, and the neutral may not be below 16 mm² Cu or 25 mm² Al.
No. A capacitor bank corrects reactive power; it does not remove harmonic currents from the neutral.
Spacing, arrangement, burial conditions, circuit count and reference installation method matter.
Standards, references and limitations
The calculation workflow is informed by the following publicly accessible engineering references. Use the applicable purchased IEC/EN/ELOT publications and manufacturer data for detailed design.
- Schneider Electric Electrical Installation Guide — Reference installation methods and ambient/grouping factors
- Schneider Electric — Correction and grouping factors
- Schneider Electric — Adiabatic k factors (context-dependent)
- Schneider Electric Electrical Installation Guide — Sizing the neutral conductor
- EUPEN — Technical data for LV power cables (IEC 60364-5-52 ampacity tables, second source for the tabulated ratings)
- IEC/HD 60364-5-52 — Selection and erection of wiring systems (clause 524 and Annex E concern the neutral)
- IEC/HD 60364-4-43:2023 — Protection against overcurrent