Engineering Reference · Protection

Protection Function Numbers

Fast lookup for common relay functions used in MV feeders, transformer panels and industrial protection systems.

Notation matters: IEEE C37.2-2022 defines device-function numbers and acronyms. Entries below include widely used manufacturer/application suffixes (such as N, G and T), which are not universally interchangeable. Always check the relay's CT/VT wiring, function manual and actual settings. IEEE official standard ↗
Showing 22 of 22 common functions
CodeFunctionTypical use & interpretation
21Distance protectionOvercurrent & earth faultLine impedance / zone protection

Uses apparent impedance and directional/zone logic to detect line faults.

25Synchronism-check / synchronizingControl & systemSafe connection of AC sources

Checks synchronism conditions such as voltage, frequency and phase angle before closing.

27UndervoltageVoltage & frequencyVoltage supervision and tripping

Acts when a selected voltage quantity falls below a defined setting with associated timing.

32Directional powerControl & systemReverse power and power-flow supervision

Supervises the sign or direction of active or reactive power according to the relay function.

46Negative-sequence current / phase unbalanceTransformer & machineMotor and generator protection

Detects unbalanced currents via negative-sequence or related criteria.

47Phase-sequence / phase-balance voltageVoltage & frequencyPhase rotation and voltage balance

Supervises phase sequence or voltage unbalance depending on relay implementation.

49Thermal protectionTransformer & machineThermal overload model

Models heating and/or monitors temperature to protect cables, motors or transformers.

50Instantaneous overcurrentOvercurrent & earth faultFast phase overcurrent protection

Operates for current above pickup without an intentional time delay; practical operation is not zero milliseconds.

50NInstantaneous neutral / residual overcurrentOvercurrent & earth faultEarth-fault protection

Common notation for instantaneous earth/neutral overcurrent sensing or residual-current calculation.

N denotes a device-specific neutral/residual measurement convention; confirm CT connections and manufacturer terminology.

51Time overcurrentOvercurrent & earth faultPhase-fault and overload coordination

Time-delayed overcurrent element, often inverse-time or definite-time.

51NTime neutral / residual overcurrentOvercurrent & earth faultDelayed earth-fault protection

Common notation for time-delayed neutral or residual-current protection.

N/G suffix usage is not uniform among manufacturers; confirm measurement and setting logic.

51GTime ground overcurrentOvercurrent & earth faultMeasured ground-current protection

Often denotes earth-fault protection using a dedicated ground CT input.

G and N distinctions can vary between devices.

59OvervoltageVoltage & frequencyVoltage supervision

Acts above a voltage pickup with the relay-specific measuring and timing logic.

59NNeutral displacement / residual overvoltageVoltage & frequencyEarth-fault voltage detection

Often supervises residual/zero-sequence voltage (for example calculated or measured 3U0).

Meaning and voltage reference depend on measurement wiring and relay documentation.

67Directional overcurrentOvercurrent & earth faultDirectional phase-fault protection

Combines an overcurrent element with directional information from suitable polarizing quantities.

67NDirectional earth-fault overcurrentOvercurrent & earth faultEarth faults on interconnected MV feeders

Uses residual/zero-sequence current with directional polarization appropriate to the network earthing method.

Polarizing methods and signs are relay-specific; do not infer direction from the suffix alone.

74Alarm / supervisory relayControl & systemTrip-circuit and status supervision

General alarm/supervisory function; application-specific acronyms such as TCS are often used.

79Automatic reclosingControl & systemOverhead-line auto-reclose

Performs programmed reclose attempts after a protective trip where the system permits it.

81U / 81OUnderfrequency / overfrequencyVoltage & frequencyFrequency protection

Supervises low/high frequency using defined thresholds, delays and measurement filters.

Suffix nomenclature may be shown as 81<, 81> or device-specific variants.

86Lockout / master tripControl & systemTrip memory and interlocking

Maintains a protective lockout condition until the specified manual/electrical reset sequence.

87Differential protectionTransformer & machineInternal-zone fault protection

Compares zone-boundary currents after proper CT ratio, vector and saturation considerations.

87TTransformer differential protectionTransformer & machineTransformer internal-fault protection

Common application suffix for transformer differential, including vector-group/CT compensation.

T is an application suffix; the underlying device-function number is 87.

Need the underlying standard? IEEE C37.2 scope and edition →