Imagine a water pipe. When water flows, friction causes a pressure difference along the pipe. When electric current flows through a real cable, its electrical impedance causes a voltage difference between the two ends.
This lesson explains the basic physics, how to calculate a practical approximation, and what still needs checking before selecting a cable.
What is voltage drop?
The voltage at the beginning of a cable is called the sending-end voltage. The voltage at the appliance, motor or distribution board is called the receiving-end voltage. Usually, when current flows, the receiving voltage is slightly lower.
We normally express voltage drop in volts (V) and as a percentage (%) of nominal supply voltage. The calculator estimates the in-phase voltage magnitude difference for one feeder under the stated assumptions.
Why should we care?
Every real conductor has impedance. If the voltage reaching a load is too low, equipment may malfunction, motors may deliver less starting torque, and equipment performance may suffer. Excessive conductor resistance also produces heating losses, but voltage drop and cable heating are separate design checks.
Supply quality
At the loadEquipment needs voltage within a suitable operating range.
Load current
More current, more dropA heavily loaded cable generally has a larger voltage drop.
Cable route
Longer means more dropThe same conductor has more total impedance over a longer run.
Think of voltage drop as only one item on the cable-design checklist. The cable must also have sufficient ampacity, fault withstand and appropriate protection.
Why three-phase, single-phase and DC differ
Our calculator supports three common arrangements. Choosing the right arrangement matters because each uses a different voltage reference and conductor-path multiplier.
Balanced three-phase AC
Use line-to-line voltage (L-L), normally 400 V in a European 230/400 V system. For a balanced load, the line-to-line drop approximation includes a √3 multiplier.
Single-phase AC, two wires
For a typical line-to-neutral circuit use line-to-neutral voltage (L-N), normally 230 V. Current travels to the load and returns through the neutral, so we use a factor of 2 when the conductors have equal impedance.
DC, two wires
There is no AC phase angle or inductive reactance term in this simple steady-state calculation. The outgoing and returning wires both contribute resistance.
Current and length — the easy part
I is load current measured in amperes (A). L is the one-way route length from the supply to the load. In our equations resistance and reactance are in Ω/km, so we convert metres to kilometres.
For example, a 50 m cable run means L = 0.05 km. Do not double that input: the single-phase and DC equations already account for the return conductor.
What is resistance, and why does temperature matter?
Resistance R describes how strongly a conductor opposes current. Copper typically has lower electrical resistivity than aluminium of the same cross-sectional area. A larger conductor gives current more cross-section to flow through, lowering resistance.
Here A is conductor area in mm², ρ₂₀ is reference resistivity in Ω·mm²/m, and the 1000 converts Ω/m to Ω/km. Real cables are made to a standard: IEC 60228 sets a maximum DC resistance for each size, which is typically 5–7 % higher than the ideal-metal value above. The calculator therefore offers a resistance source selector: the default pure-metal estimate, the IEC 60228 maximum (conservative, for sizes tabulated in the built-in data), or a manufacturer value. If a size is not tabulated, the calculator tells you it fell back to the resistivity estimate.
Conductors get more resistive as they warm up. The following linear correction is commonly used as a first approximation:
What changes when cables run in parallel?
Large feeders often need several conductors connected to the same phase. For example, 3 × 240 mm² copper per phase means three 240 mm² conductors share phase L1, three share L2 and three share L3. You do not enter 720 mm² as one conductor: select 240 mm² and 3 parallel runs.
Enter the total feeder current. If identical parallel paths have equal impedance, each carries the total current divided by the number of runs.
Example: 900 A in three parallel runs
Under the same ideal equal-sharing assumption, the equivalent feeder resistance is the resistance of one conductor divided by three. In a simplified equivalent-reactance model we also divide X by three.
The calculator uses equivalent R and X with total current, which is mathematically equivalent to using each run’s impedance with its share of current when the paths are identical.
For further reading, see the Schneider Electric guide to conductors in parallel ↗.
What is cable reactance, and where does cos φ fit?
With alternating current, a cable also has inductive reactance X, related to magnetic fields around conductors. Its value depends on geometry, spacing and system frequency. A common illustrative LV estimate is 0.08 Ω/km, but it is not accurate for every cable.
The load current may lag behind or lead the voltage. This is the phase angle φ, closely related to power factor cos φ. Both R and X contribute to the voltage-drop projection, but by different amounts.
Use + for a lagging inductive load and − for leading capacitive current in this approximate relationship. A sufficiently leading load can yield a negative calculated drop (voltage rise). That requires more detailed verification rather than treating it as an automatic design approval.
The voltage-drop equations
For one uniform AC feeder, calculate the conductor impedance contribution, multiply by load current and one-way length, then apply the circuit multiplier.
From volts to percentage
For three-phase use L-L nominal supply voltage; for the typical single-phase circuit use L-N voltage; for DC use the DC supply voltage.
Let's calculate a 400 V feeder
32 A over 50 m, copper 10 mm²
Assume 400 V L-L, conductor temperature 70 °C, cos φ = 0.90 (lagging), and X = 0.08 Ω/km.
Results are calculated from full-precision inputs. Intermediate displayed numbers are rounded.
Change these values in the calculator →How much voltage drop is acceptable?
How long can this cable be?
Voltage drop grows in direct proportion to length, so the calculator can also tell you the longest one-way length at which this cable just reaches your drop limit. It rearranges the same equation, where the coefficient k is √3 for three-phase and 2 for single-phase or DC:
For the example circuit above (32 A, 50 m, 10 mm² copper, 5 % limit), the longest length is about 191 m. This number answers one question only: how far the cable can go before voltage drop alone is exceeded. The cable must still pass its ampacity and short-circuit checks, which is what LV Cable Sizing is for. If the load is leading the reactive term can cancel the resistive drop, and then no length reaches the limit; the calculator says so instead of printing a number.
There is no single percentage appropriate for every project. The permissible drop depends on the supply arrangement, circuit use, national adoption of standards and any more demanding equipment specification.
As background, the informative guidance associated with IEC 60364-5-52 is commonly presented with examples such as 3% for lighting and 5% for other uses on installations supplied directly from a public LV supply. Other categories have different recommendations and conditions. These are not universal approval thresholds for every feeder.
KiloVolt therefore lets you enter your own voltage-drop target. The on-screen check compares the calculated percentage with that value; it does not certify compliance with any particular installation standard.
Authoritative references
IEC 60364-5-52:2009+A1:2024 — Wiring systems (IEC webstore) ↗
Schneider Electric Electrical Installation Guide — Voltage-drop calculation ↗
Schneider Electric Electrical Installation Guide — Voltage-drop guidance ↗
When the result is not feasible. The formulas are linear and assume a constant current. If the calculated drop reaches the supply voltage (100 %), the voltage at the load would be zero or negative. That is outside what this normal-load approximation can describe, although a real circuit can reach zero terminal voltage, for example in a fault, where the constant-current assumption no longer applies. KiloVolt then shows “Not feasible” instead of numbers, and still gives the maximum length for your target. Above 20 % the figures are shown with a caution, because the constant-current assumption is already unreliable; that threshold is a judgment, not a standard. In both cases the fix is a larger cross-section, more parallel runs, a shorter length or a lower current.
Common mistakes to avoid
Enter the one-way cable length. The factor 2 already accounts for a two-wire return circuit.
Use the nominal reference that matches the formula: 400 V L-L for typical three-phase LV and 230 V L-N for line-neutral circuits.
Resistance increases with conductor temperature. A warm cable usually has a larger drop.
Reactance varies with cable configuration, spacing and frequency. Replace illustrative values with verified cable data when needed.
Additional runs lower ideal resistance but do not guarantee equal current sharing or enough ampacity. The layout, terminations and grouping factors still matter.
Still verify installation ampacity, protection, thermal short-circuit withstand, disconnection requirements and any applicable national rules.
Three-phase imbalance, harmonics, distributed loads and motor starting can require more detailed calculations.
Try your own cable and load
Change voltage, current, cable length, conductor material and temperature, then see every step of the result.