VFD Sizing
Required continuous output current and candidate checks.
VFD output-current sizing
The drive's continuous output current, after its own derating, must cover the motor's rated line current. Mains input current, overload need, PWM effects and EMC are separate checks that this tool does not assess.
Motor
Output-current method for a three-phase induction motor. The motor current comes from the nameplate when you enter it, otherwise from the built-in reference.
Three-phase motor. This tool covers three-phase motors only.
Advanced: nameplate and motor data (all optional)
Anything you enter here replaces the built-in reference model for that quantity. Leave a field empty to use the reference where it applies.
Advanced: check a candidate drive (optional, manufacturer data)
Enter only what the drive's documentation gives, after its own derating for ambient, altitude and switching frequency. Anything missing stays NOT ASSESSED, and there is never an overall PASS.
Results
- Drive suitability, until a candidate with manufacturer data is entered
- Mains input current, harmonics and the upstream protection (need the drive's input rating)
- Overload need of the load and the starting torque
- Motor insulation under PWM (dv/dt), long motor cables, output reactors or sine filters, bearing currents
- EMC filter, RCD type, braking resistor, safety functions and ambient or altitude derating
1. Efficiency, power factor and locked-rotor ratio in use
Entered values replace the reference. The reference (IE3, 4 poles, 50 Hz, 400 V family) is the plain mean of two catalog series. Efficiency: two-series reference; power factor: two-series reference; Is/In: two-series reference.
2. Rated line current (three-phase)
Mechanical output power divided by the electrical quantities at the rated operating point.
3. Delta winding current (rated running, only if the motor runs in delta)
In a balanced delta connection each winding carries the line current divided by √3. This is the rated RUNNING winding current; it is not a starting current and does not depend on the starting method. In-line starters and drives are sized from the LINE current, never from this value.
4. Input, apparent and reactive power
Sinusoidal rated operating point.
5. Nominal VFD motor-side current reference
A nominal motor-side reference equal to the rated current. It is NOT a start-current prediction and NOT the mains input current of the drive.
Calculations use full precision internally; the displayed numbers are rounded for readability.
Related: Motor Current & Starting · Soft Starter Sizing · AC Power · Voltage Drop · LV Cable Sizing