Motor Current & Starting
Rated and delta winding current, and four starting-method figures.
Rated current, delta winding current and starting-method figures
Enter the motor power and voltage, or the nameplate current in Advanced. The built-in reference is a two-series IE3 four-pole estimate, not your motor's data. The four starting-method figures are different quantities: none is a protection or sizing value.
Motor and starting method
Defaults: a three-phase 15 kW motor on 400 V, 50 Hz, with the built-in IE3 four-pole reference. Enter the nameplate values in Advanced when you have them.
Advanced: nameplate and motor data (all optional)
Anything you enter here replaces the built-in reference model for that quantity. Leave a field empty to use the reference where it applies.
Results
1. Efficiency, power factor and locked-rotor ratio in use
Entered values replace the reference. The reference (IE3, 4 poles, 50 Hz, 400 V family) is the plain mean of two catalog series. Efficiency: two-series reference; power factor: two-series reference; Is/In: two-series reference.
2. Rated line current (three-phase)
Mechanical output power divided by the electrical quantities at the rated operating point.
3. Delta winding current (rated running, only if the motor runs in delta)
In a balanced delta connection each winding carries the line current divided by √3. This is the rated RUNNING winding current; it is not a starting current and does not depend on the starting method. In-line starters and drives are sized from the LINE current, never from this value.
4. Input, apparent and reactive power
Sinusoidal rated operating point.
5. Estimated locked-rotor current (DOL)
Standstill RMS line-current estimate at rated voltage: I_n × Is/In. It excludes the first-cycle asymmetrical peak, the duration of the start, any voltage dip and whether the load accelerates.
Calculations use full precision internally; the displayed numbers are rounded for readability.
Related: Soft Starter Sizing · VFD Sizing · AC Power · Voltage Drop · LV Cable Sizing