Ohm's law
V · A · ΩVoltage equals current times resistance.
DC or a purely resistive AC element; V in volts, I in amperes, R in ohms.
Useful electrical equations with the conditions under which they're valid. Every formula connects to a working KiloVolt calculator.
Voltage equals current times resistance.
DC or a purely resistive AC element; V in volts, I in amperes, R in ohms.
Magnitude of inductive opposition to sinusoidal AC.
Ideal inductor; f in Hz and L in H gives XL in Ω.
Magnitude of capacitive reactance.
Ideal capacitor; f in Hz and C in F gives XC in Ω. Capacitive impedance has a negative imaginary sign.
Magnitude of complex series impedance R+jX.
R and X must be at the same frequency and referred to the same electrical circuit; useful for LV impedance and voltage-drop approximation.
First-order resistivity change with conductor temperature.
Temperature in °C, α20 matched to conductor material near reference temperature; account for AC skin/proximity effects separately.
Approximate feeder voltage drop along one phase length.
Balanced sinusoidal three-phase system, R/X per unit length and L in matching units. Neglects higher-order phasor effects.
Approximate outgoing-and-return voltage drop for a two-wire single-phase feeder.
Same conductor size and temperature in both legs, sinusoidal AC; use matching impedance-length units. DC uses R term only.
Equivalent phase impedance of n identical balanced parallel cable runs.
Identical length, conductor type, installation and equal current sharing; unequal impedances require explicit current distribution.
Reference cable ampacity adjusted by applicable installation factors.
Correction factors must match the specific cable construction, installation method, ambient/soil temperature and grouping. Not a universal independent multiplier model.
Open-circuit string voltage corrected to a design cell temperature.
Temperature coefficient as fractional 1/°C, identical series modules, applicable manufacturer model and conservative minimum design cell temperature. Do not use ambient and cell temperature interchangeably.
Current available from identical parallel PV strings at the MPPT.
Identical string models and matched operating conditions; verify per-input and combined MPPT operating and Isc limits separately. Current-limited MPPT may clip.
Electrical power for a resistive element.
DC or resistive sinusoidal AC RMS values. V in volts, I in amperes, P in watts.
Apparent power of a single-phase circuit.
RMS voltage across load and RMS current; S in VA, U in V.
Three-phase apparent power using line-to-line voltage and line current.
Balanced sinusoidal system; S in VA, ULL in V, IL in A.
Active input power for a balanced sinusoidal three-phase load.
Fundamental sinusoidal quantities; cos φ is displacement power factor. Harmonics require additional consideration.
Connects apparent, active and reactive power.
Sinusoidal steady state with consistent sign/magnitude conventions. Distortion power not included.
Ideal capacitive kvar required to reduce positive inductive reactive power.
Same active power before/after, sinusoidal, both states lagging; P in kW gives Qc in kvar.
Neutral maximum expected RMS current must not exceed its corrected continuous ampacity.
Corrected ampacity must reflect installation method, grouping, conductor temperature, neutral harmonic loading and applicable protection. This alone does not authorize a reduced neutral.
The neutral carries the vector imbalance of the phase fundamental currents.
Complex fundamental RMS phasors referenced consistently. Triplen harmonic neutral current may add arithmetically and must be evaluated separately.
Useful output power divided by input power.
Use consistent active-power quantities and defined operating point; efficiency varies with load and temperature. Percent efficiency is 100η.
Reactive component in a sinusoidal balanced three-phase load.
Sinusoidal waveform, RMS ULL and line current; sign convention for capacitive/inductive Q must be declared.
Installed PV rating from individual module STC power.
Same rated module power for the counted group; sum independently if module models differ. STC nameplate does not predict instantaneous in-field output.
Nameplate installed DC module rating divided by rated inverter AC active power.
Use consistent kW bases. No universal allowable maximum; respect manufacturer voltage, current, PV capacity and thermal limits.
First-order estimated monthly energy from irradiation on the module plane.
P in kWp, H in kWh/m²/month relative to 1 kW/m², PR dimensionless with consistent loss boundary. Monthly totals cannot establish clipping or battery dispatch.
Discrete battery energy conservation when charge/discharge energies are measured outside the battery.
Consistent AC/DC energy boundary, time step, efficiency convention and SOC limits required. Cannot be simulated reliably from monthly generation/load totals alone.
Discounted annual incremental benefit net of initial cost.
Use realistic lifecycle maintenance, replacements, degradation, export compensation, tariffs and discount rates; monthly-only dispatch scenarios are preliminary.
Reactive-power magnitude for three identical delta capacitors.
Balanced, ideal three-phase capacitors; CΔ is the capacitance of ONE delta branch in farads, voltage in V, Q in var.
Ideal equivalent capacitance measured between two line terminals.
Balanced, isolated capacitor-only bank with third line floating, no reactors, bleed resistors affecting measurement or external circuits. Not universal to real equipment.
Nominal current on one side of a three-phase transformer.
Sn in VA and side rated line-to-line voltage in V; use nameplate data, no cos φ input.
Transformer equivalent impedance magnitude referred to the selected side.
uk is short-circuit impedance percent on rated base, S in VA, U in V; phase angle and R/X not given by uk alone.
Preliminary cross-sectional area to withstand conductor I²t heating.
Current in A, time in s, k in A·√s/mm² for actual material and initial/final temperatures; does not verify mechanical withstand or protective clearing.
Apparent three-phase short-circuit level at a stated voltage.
Use compatible ULL in V and fault current Ik in A for VA. Does not calculate fault current on its own.
Approximate balanced three-phase initial symmetrical current from series complex impedances.
Preliminary IEC 60909-oriented screen, not a full fault study; impedances must be referred to one voltage level in ohms. Account separately for motors, corrections, earth faults and minimum fault conditions.
Relates prospective peak current to initial symmetrical fault and R/X dependent factor.
Simplified network-dependent peak screening only; use correct IEC 60909 calculation method and device Icm/peak withstand to verify.
PE area needed for fault thermal withstand.
Applicable only to the permitted adiabatic conditions with protective fault current/let-through I²t and k matched to material, insulation and temperatures. Verify mechanical minima and continuity.
Simplified geometric PE rule under the applicable IEC 60364-5-54 table conditions.
Same applicable material and installation assumptions. Sizes in mm². Confirm proper rounding to installed standard section and verify independent thermal/mechanical constraints.
Nameplate short-circuit voltage magnitude decomposes into resistive and reactive contributions.
Same rated base and temperature reference; load losses or test data are required to estimate uR.
No-load losses plus load-dependent winding loss at per-unit load x.
Approximate at rated voltage/frequency, constant temperature and rated reference copper loss; stray losses and harmonics may require explicit treatment.
| Symbol | Prefix | Factor |
|---|---|---|
| G | giga | 10⁹ |
| M | mega | 10⁶ |
| k | kilo | 10³ |
| m | milli | 10⁻³ |
| µ | micro | 10⁻⁶ |
| n | nano | 10⁻⁹ |
| p | pico | 10⁻¹² |
1 MVA = 1,000 kVA
1 kA = 1,000 A
1 mH = 0.001 H
1 µF = 0.000001 F
1 kΩ = 1,000 Ω
Use k (lowercase) for kilo and M (uppercase) for mega. kVA, kW and kvar describe different power quantities.
Source: NIST Guide to the SI ↗